Description
Outdoor DC UPS Backup Power:
AC Current (Typical)7A/115VAC – 3.5A 230VACInrush Current (Typical) Cold Start 60AShort CircuitO/P Built in Fuse (FS100)Reverse PolarityBy Internal FuseOver Voltage>16 ~ 18V
Shuts Down O/P Voltage. Re-Power On to Recover
Safety StandardsIEC60335-2-29 CB approved by TUV(except for 48V),
UL60950-1, EAC TP TC 004 approvedWithstand Voltage I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVACIsolation Resistance I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25/ 70%
RHEMC EmissionCompliance to EN55032 (CISPR32) Class B, EN61000-3-2,-3
(only P type),EAC TP TC 020EMC ImmunityCompliance to EN61000-4-2,3,4,5,6,8,11, EN55024, light
industry level, criteria A,EAC TP TC 020
Enclosure Specs |
|
---|---|
Enclosure Size | H 30” x W 22” x D 13” |
Battery Capacity | (4) 100Ah Batteries |
100Ah Battery Size* | H 9.2” x W 12.3” x D 6.7”
*Battery Sizes are “Typical”. We cannot guarantee that |
Enclosure Weight | 33 LBS |
Recommended Pole Size | 4″ to 6″ Schedule 40 Rigid Metal Pole |
Material | Powder Coated Aluminum |
Operating Temp | -40° F to +140° F (-40° C to +60° C)
Batteries can lose up to 50% of power in temperatures |
Boost Charge Voltage | 14.4V |
Float Charge Voltage | 13.6V |
Voltage Adjustment Range | 13 ~ 14.7V |
Battery Type | Sealed Lead Acid (SLA) |
Output Current (Typical) | 24.3A |
Voltage Range | 90 ~ 132VAC / 180 ~ 264VAC Selected by Switch |
Frequency Range | 47 ~ 63Hz |
Power Factor (Typical) | > 0.65 (with P type) @ 230VAC |